Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*CHASE NIPPLES NOT APPROVED FITTING WITH LB-SUBPANEL CLEAN SURFACE UNDER LUG-PV DISCONNECT USE APROVED CONNECTIONS FOR COPPER TO ALUMINUM DISSIMILAR METALS AT PV ARRAYS |
|
| 08/30/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CHASE NIPPLES NOT APPROVED FITTING FOR USE WITH LB 2) ONLY ONE CONDUCTOR TO A LUG-PV DISCONNECT 3) REMOVE TEFLON TAPE FROM FITTINGS TO MAINTAIN GROUNDING CONNECTIONS 4) PLEASE USE A WIRE TERMINAL END FOR STRANDED WIRE 5) STRAP CONDUIT TO LB AT ROOF EDGE |