Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2ND FLOOR PENETRATION FIRE STOPPED 2) CLIP JOISTS AND STUDS AT INTERIOR BEARING WALL 3) MOVE WIRES AND FIREBLOCK LOWER STAIRS 4) ENLARGE HOLE IN OSB WHERE HOME RUNS ENTER PANEL 5) WIRE EXHAUST FAN IN POWDER ROOM 6) REMOVE NAILS BEHIND VENT IN KITCHEN 7) LIGHT IN STAIRWAY TO LOW 6'-8" MIX CLEARANCE TO BOTTOM OF FIXTURE 8) PROVIDE DETAIL FOR CUT FLOOR TRUSS AT LET IN STUDS IN 2ND FLOOR STAIR RAILING |
|
| 11/17/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) RED HEAD ANCHOR BOLT AND ANCHOR BOLTS LOOSE 2) HOLDOWNS LOOSE 3) NOTE C SHEARWALL P-3 NOT DONE 4) WATER HEATER B-VENT WITHIN 1" COMBUSTIBLES 5) WATER HEATER VENT ABOVE CEILING 6) LSL SUPPORT MISSING 7) P-3 SHEARWALL MISSED STUD 8) STOPPED INSPECTION |