Permit: T05CM02195

Parcel: 140376960


Addresses:

7049 S HARRIER LP

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
12/13/2005 SHEET ROCK NAILING Approved IVRS - Inspection :*
12/09/2005 SHEET ROCK NAILING Denied IVRS - Inspection :
The drywall is not nailed per code.| 175*
1) OK TO TAPE ALL BUT REPAIR AREAS
2) GARAGE CEILING NOT NAILED AT 6" ON CENTER PER IRC TABLE 702.3.5 NOTE: E BELOW OCCUPIED SPACE
3) PROVIDE PROOF OF EXTERIOR CLIP APPROVAL
4) ONE STUD NOT NAILED BEDROOM 2 SHEARWALL G-3