Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2005 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 05/19/2005 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL COVER SOUTH SIDE (MECH FLEX) STICKING OUT OF WALL 2) UNCOVER SEWER TO EXISTING CONNECTION 3) PAINT EXPOSED ABS PIPING EXTERIOR 4) ELEVATE AND SECURE DISHWASHER DRAIN LINE 5) INSTALL FLUE H20 HEATER AND METAL ENCLOSURE 6) INSTALL APPROVED HAND RAILS AND GUARD RAILS STAIRS (SAFETY ISSUES) 7) 30" CLEARANCE TOILET H20 CLOSET ROOM 8) HAVE SUB-PANEL REMOVED FROM PLAN-NOT USED 9) STOPPED INSPECTION-COMPLETE ALL TO CODE AND PLAN 10) ITEM 03040 EXISTING-NO INSPECTION REQUIRED PER PAPERWORK TURNED IN BY INSPECTOR R. O'HAVER 10) RECALL |
|
| 05/16/2005 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVISE DRAWINGS TO REFLECT AS BUILT, WITHIN DEMENSIONS 2) COMPLETE PLUMBING INSTALLATIONS 3) 30" CLEARANCE REQUIRED AT WATER CLOSET COMPARTMENT 4) ANTI-TIP MISSING AT STOVE 5) ELECTRIC OUTLET AT KITCHEN COUNTER NOT TO CODE 6) ALL ELECTRIC CONNECTION SHALL TERMINATE IN BOXES IN ATTIC |