Permit: T05CM02180

Parcel: 12604022C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM02180

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) MAKE YARD CLEANOUTS WATER AND GAS TIGHT LABEL GRAY WATER-NON POTABLE DO NOT DRINK
05/23/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV W/TEST IS OK.
PEX WATER PIPING W/80 PSI IS OK IN WALLS -
EXCEPT AT WH STUB OUTS. PEX MANUFACTURER REQUIREMENTS SPECIFY 18" OF METALLIC PIPE BETWEEN SWEAT VALVES & FITTINGS.
WATER FLEXES & VALVES ARE SUBJECT TO REPLACEMENT THEREFORE 18" IS NECESSARY TO PREVENT DAMAGE TO PEX.
PROVIDE WATER TEST ON TUB WASTE & OVERFLOW CONNECTIONS.
SECURE CLOSET FLANGES TO FLOOR.