Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM02180
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) MAKE YARD CLEANOUTS WATER AND GAS TIGHT LABEL GRAY WATER-NON POTABLE DO NOT DRINK |
|
05/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV W/TEST IS OK. PEX WATER PIPING W/80 PSI IS OK IN WALLS - EXCEPT AT WH STUB OUTS. PEX MANUFACTURER REQUIREMENTS SPECIFY 18" OF METALLIC PIPE BETWEEN SWEAT VALVES & FITTINGS. WATER FLEXES & VALVES ARE SUBJECT TO REPLACEMENT THEREFORE 18" IS NECESSARY TO PREVENT DAMAGE TO PEX. PROVIDE WATER TEST ON TUB WASTE & OVERFLOW CONNECTIONS. SECURE CLOSET FLANGES TO FLOOR. |