Permit: T05CM02180

Parcel: 12604022C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM02180

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SMOKE DETECTORS TO BE AS PER 210.12
2) WATER HEATER TO HAVE DISCONNECTING MEANS
3) CHASE NIPPLE NOT AN APPROVED FITTING
4) TIGHTEN LOOSE FITTINGS A/C'S
5) #8 NM CABLE AMPACITY TO BE PER CODE 334.80
6) PANEL SCHEDULES NOT REFELCTIVE OF WORK INSTALLED