Permit: T05CM02166


Addresses:

2821 N FORGEUS AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/02/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/13/2009 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
01/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE FLEX 12"
2) NO ELECTRICAL PLAN FOR 2ND FLOOR STORAGE ?
3) COMPLETE ALL WIRE MAKE UP AT BOXES
4) NEED TO GROUND ALL METAL BOXES WITH APPROVED METHOD
5) NEED TO SEPERATE NEUTRALS FROM GROUNDS AT SUB PANEL
6) NEED A GROUNDING CONDUCTOR GOING BACK TO MAIN PANEL (INSULATED)
7) NEUTRALS AND GROUNDS DBL LUGGED (SEPERATE)
8) SECURE EMT WITHIN 3' FT OF BOXES
08/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ANSWER AT DOOR
NO MESSAGE
02/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*