Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/24/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SHALL HAVE FIRE SPRINKLER APPROVAL & MECHANICAL INSP. APPROVAL FOR GAS TO NEW PAINT BOOTH |
|
| 02/01/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) 15 PSI TEST ON EXISTING SYSTEMS (2) WITH EXTENSION OF GAS PIPING FROM EXISTING METER LOCATION TO NEW METER LOCATION OK 2) GAS CARDS AND APPROVED PLAN ON SITE 3) SHALL PROVIDE REVISED APPROVED GAS ISOMETRIC OF (2) EXISTING SYSTEM AND NEW SYSTEM TO NEW PAINT BOOTH |