Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TEMPERED WINDOW MISSING 2) SEAL ALL PENETRATIONS (LATH) 3) NO TEST ON DWV'S 4) NAIL PROTECT ALL ELECTRIC WITHIN 1 1/4 FROM EDGE OF STUD 5) REPLACE TRIMMERS UNDER WEST WINDOW 6) STOPPED INSPECTION-NEXT FAILURE WILL RESULT IN A REFEE |
|