Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM02129
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2005 | MECHANICAL - INTERMEDIATE | Approved | ||
08/08/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A PERMIT FOR THE NEW A/C UNIT ON THE ROOF 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 3) YOU CAN TERMINATE TO THE LAV TAIL PIECE 4) ELECTRIC DISCONNECT IS BLOCKING ACCESS TO SERVICE PANEL 5) RELOCATE AS NEEDED 6) MUST HAVE A MINIMUM 30" CELARANCE 7) PROVIDE A FRESH AIR INTAKE 8) SUPPORT WATER LINE TO EVAP COOLER |