Permit: T05CM02129

Parcel: 135074550

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/04/2005 MECHANICAL - INTERMEDIATE Approved
08/08/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A PERMIT FOR THE NEW A/C UNIT ON THE ROOF
2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
3) YOU CAN TERMINATE TO THE LAV TAIL PIECE
4) ELECTRIC DISCONNECT IS BLOCKING ACCESS TO SERVICE PANEL
5) RELOCATE AS NEEDED
6) MUST HAVE A MINIMUM 30" CELARANCE
7) PROVIDE A FRESH AIR INTAKE
8) SUPPORT WATER LINE TO EVAP COOLER