Permit: T05CM02126

Parcel: 140376090


Addresses:

6876 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/17/2005 FRAMING Approved IVRS - Inspection :*
11/14/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) WATER T & PLINE MUST EXHAUST BETWEEN 6" + 18" ABOVE SLAB OR GABLE
2) HOUSE INSPECTED USING 1212 PLAN P02-M0216 WITH PAGES S-1, S-1.1, S-1.2, S-2, S-2.1, S-2.2, S-2.3, S-3, S-3.1, S-4, SD-1, SD-2, SD-3 AND SD-4 NOT APPROVED BY CITY OF TUCSON. INSPECTIONS MADE AT DIRECTION OF HECTOR LEYVA
3) NO DWV WATER TEST
4) FIRE STOP SECOND FLOOR PENETRATIONS
5) PROVIDE 1/2" CLEARANCES WIRES TO WATER HEATER "B" VENT
6) PROVIDE 2 X LEDGER TO SUPPORT STAIR PER 49/AD3
7) MAXIMUM ALLOWED STAIR RISER IS 7 3/4" EXCEED TO 8"
8) 3/8" DIFFERENCE MAXIMUM ALLOWED BETWEEN STAIR RISERS EXCEEDED MINIMUM 7 1/4" MAX 8"
9) STOPPED INSPECTION-TO MANY ITEMS
10) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
11/08/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) PLANS DO NOT HAVE CITY OF TUCSON APPROVAL ON JORDAN ENGINEERING PAGES S-1 THRU SD-4
2) 1" CLEARANCE REQUIRED BETWEEN WATER HEATER "B" VENT AND COMBUSTIBLE MATERIAL
3) LIVING ROOM ELECTRIC OUTLET CANNOT BE ON KITCHEN COUNTER CIRCUIT
4) PLUMBING STACK OUT OF WALL
5) STOPPED INSPECTION-TO MANY ITEMS