Permit: T05CM02119

Parcel: 140378040

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/16/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/09/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1) GROND RODS CANNOT BE BENT. GRONUD IS SOFT ENOUGH TO DRIVE RODS FULL DEPTH. DRIVE THE GROUND RODS FULL DEPTH PRIOR TO RESCHEDULE
YOU MUST PAY A REINSPECTION FEE PRIOR TO NEXT INSP.
09/08/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
BENDING OF GROUND RODS IS NOT ALLOWED. THEY MUST REMAIN STRAIGHT. NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
09/07/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
GROUND RODS MUST BE DRIVEN VERTICALLY
09/06/2005 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
PER TIM
08/31/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
NO UFER GROUND INSTALLED