Permit: T05CM02105


Addresses:

966 W CALLE CARASOL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/16/2005 FRAMING Approved IVRS - Inspection :*
09/15/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
PER SUPER
09/13/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE APPVD. REPAIR FOR DBL TOP PLATE AT KITCHEN
2) BLOCK MECH IN KITCHEN, MASTER B/R
3) PROVIDE 12" CLEARANCE FOR PEX FROM CAN LIGHTS
4) BLOWN FIRE BLOCKS
5) NAIL PROTECT WATER LINES AT MASTER TOILET
6) 10 EA LDI'S AT MASTER AREA DAMAGED
7) STUDS ABOVE DOORS CUT
8) NO TEST ON DWV'S
9) FIRE BLOCK MISSING AT HALL BATH AREA
10) BLOCK CHASE AT KITCHEN
09/12/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE: PLEASE CALL IN LATH AND WINDOW INSPECTIONS WITH INTERMEDIATES
1) NO TEST ON DWVS, OR WATER LINES
2) INTERIOR HOLD DOWNS NOT INSTALLED
3) PROVIDE 12" CLEARANCE FOR WATER LINES FROM CAN LIGHTS
4) DBL TOP PLATE AT INTERIOR BEARING WALL OVERNOTCHED PROVIDE APPVD REPAIR
5) COMPLY WITH DETAIL 6-6.2
STOPPED INSPECTION