Inspection History Details
Permit: T05CM02105
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/15/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* PER SUPER |
|
| 09/13/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE APPVD. REPAIR FOR DBL TOP PLATE AT KITCHEN 2) BLOCK MECH IN KITCHEN, MASTER B/R 3) PROVIDE 12" CLEARANCE FOR PEX FROM CAN LIGHTS 4) BLOWN FIRE BLOCKS 5) NAIL PROTECT WATER LINES AT MASTER TOILET 6) 10 EA LDI'S AT MASTER AREA DAMAGED 7) STUDS ABOVE DOORS CUT 8) NO TEST ON DWV'S 9) FIRE BLOCK MISSING AT HALL BATH AREA 10) BLOCK CHASE AT KITCHEN |
|
| 09/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: PLEASE CALL IN LATH AND WINDOW INSPECTIONS WITH INTERMEDIATES 1) NO TEST ON DWVS, OR WATER LINES 2) INTERIOR HOLD DOWNS NOT INSTALLED 3) PROVIDE 12" CLEARANCE FOR WATER LINES FROM CAN LIGHTS 4) DBL TOP PLATE AT INTERIOR BEARING WALL OVERNOTCHED PROVIDE APPVD REPAIR 5) COMPLY WITH DETAIL 6-6.2 STOPPED INSPECTION |