Permit: T05CM02085

Parcel: 133090590


Addresses:

7885 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM02085

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
1. FINISH CAN SUPPORT WIRES - CHECK ON FINAL
03/07/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. JUNCTION BOX COVERS TO BE ACCESSIBLE
2. SUPPORT M/C COVER 6' INTERVALS
3. SUPPORT VDV CABELING NOT LAYING BETWEEN STRUCTURAL MEMBERS.
4. SUPPORT WIRES NEEDED FOR RECESSED CANS.
5. SUPPORT EMT CONDUIT WITHIN BOXES AS PER 358.50 (A)