Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM02085
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE 1. FINISH CAN SUPPORT WIRES - CHECK ON FINAL |
|
03/07/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. JUNCTION BOX COVERS TO BE ACCESSIBLE 2. SUPPORT M/C COVER 6' INTERVALS 3. SUPPORT VDV CABELING NOT LAYING BETWEEN STRUCTURAL MEMBERS. 4. SUPPORT WIRES NEEDED FOR RECESSED CANS. 5. SUPPORT EMT CONDUIT WITHIN BOXES AS PER 358.50 (A) |