Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2006 | ROOF NAILING | Approved | IVRS - Inspection :* 1) OK TO LOAD |
|
| 04/05/2006 | ROOF NAILING | Partial Approval | IVRS - Inspection :* 1) A HUS 26 HANGERS REQUIRED 16D COMMONS 2) MISSED 4' JOINT NAILING WEST SIDE 3) ALL OSB TURNED PARALLEL TO TRUSSES, BLOCK EDGE 4) NORTH END TRUSS IS CONTINOUS BEARING, SEE PLAN INSPECTOR (FOR FTG END WALL) OR TRUSS MANUFACTURER FOR SOLUTION 5) INSTALL ALL RAT RUNS 6) NORTH END TRUSSES WITH VERTICAL ? 12/6 SPLITS IN LUMBER VERT LEG 7) REQUIRES BOUNDRY NAILING, ADD BLKS SEE DETAIL 8) NEED PONY WALL FOR 3 PT BEARING A-7 TRUSSES 9) BRACING OF END TRUSSES 10) 9/6 DOESN'T SHOW VERT LEG ON TRUSSES, ASK PLAN CHECK FOR A DETAIL OF WHAT YOU HAVE |