Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/30/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT ELECTRIC TOP PLATE SOUTH WALL, UNDER WINDOWS AND THROUGHOUT HOUSE 2) WATER HEATER VENT HAS NEGATIVE PITCH 3) NEED TRUSS LAYOUT VERIFICATION |
|
| 09/23/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO TEST ON DWV'S OR WATER LINES 2) WATER LINES NEED 6" CLEARANCE FROM B-VENTS 3) SEAL PENETRATIONS FROM 1ST TO 2ND FLOOR 4) PROVIDE APPROVED ENGINEERING FOR FLOOR TRUSSES AT GLB 5) STOPPED INSPECTION-HOUSE NOT WALKED THRU BY SUPER |