Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02076
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2005 | FRAMING | Approved | IVRS - Inspection :* | |
10/04/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATH NOT STAPLED 16" ON CENTER, SEAL ALL PENETRATIONS 2) SEE INSPECTION DATED 9/30/05 ITEMS 1, 2, 3, 4 AND 7 |
|
09/30/2005 | FRAMING | Partial Approval | IVRS - Inspection :* | |
09/23/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ROMEX WITHIN 8" FROM BOX AT KITCHEN 2) NO TEST ON DWV'S OR GAS LINE 3) FIREBLOCK CHASE AT KITCHEN 4) BLOCK MECHANICAL AT POWDER ROOM 5) 3" CLEANOUT MISSING AT POWDER ROOM 6) DETAIL 4SD2 DOES NOT MATCH FRAMING 7) SEAL PENETRATIONS FROM 1ST TO 2ND FLOOR 8) NAIL PROTECT ELECTRIC AT TOP OF STAIRS 9) EXHAUST FAN MISSING AT LAUNDRY 10) REMOVE SCREEN FROM DRYER VENT 11) NAIL PROTECT VTR N/W CORNER 12) SEAL MECH CHASE |