Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02066
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2005 | FRAMING | Approved | IVRS - Inspection :* | |
10/03/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLOOR TRUSS REPAIR DAMAGED 2) PROVIDE APPROVED TRUSS REPAIR 3) FIRE BLOCK MECHANICAL CHASE 4) PROVIDE TRUSS REVISION 5) RETURN AIR IN ATTIC ACCESS AREA 6) F.T. NOT BEARING ON TWO KINGS AT STAIRS 7) B-VENT HAS NEGATIVE PITCH 8) SHIM HEADERS WHERE NEEDED 9) NO TEST ON ? LINE 10) DWV'S OK 11) STOPPED INSPECTION |
|
09/13/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE BLOCK CHASE IN GARAGE TO HOUSE 2) LEAK AT ABS VENT UPSTAIRS BY KITCHEN 3) W.H. B-VENT HAS NEG SLOPE 4) COMPLY WITH STAIR DETAIL 5) FLOOR TRUSSES INSTALLED BACKWARDS 6) PROVIDE 2X6 CONTINUOUS STRONGBACK PER TRUSS CALCS 7) STOPPED INSP |
|
09/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATH NOT COMPLETE 2) EXT CLIPS NOT APPVD |