Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM02063
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2005 | FRAMING | Approved | IVRS - Inspection :* | |
09/30/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT ABS AT MASTER BATH 2) ROOF PATIO NOT DRIED IN (DECK) 3) S.G.D. MISSING 4) SUPPORT 90 DEGREE ABS 5) NAIL PROTECT ELECTRIC IN KITCHEN |
|
09/23/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL LATH PENETRATIONS 2) PROVIDE APPROVED ENGINEER REPQIR FOR CABLE AT NORTH WEST CORNER OF GARAGE AND N/E SIDE 3) LATH STAPLES MISSING THROUGHOUT, BACK PATIO AREA NOT DONE 4) S.G.D. MISSING 5) SMOKE DETECTOR MUST HAVE 36" IN CLEARANCE FROM REGISTER 6) LEAK AT KITCHEN WATER LINES 7) NEED NEW TRUSS CALC'S 8) DWV'S OK 9) HANGERS MISSING NAILS 10) FRESH AIR AT MASTER DAMAGED |
|
09/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN ANCHOR BOLTS THROUGHOUT 2) NAIL PROTECTION THROUGHOUT 3) CLAMP GAS LINE IN LAUNDRY 4) BLOCK HVAC ABOVE STAIRS 5) SUPPORT VENT 90 DEGRESS TO ROOF ABOVE TUB 6) SUPPORT HDR IN NW BEDROOM 7) SHIM UNDER TRUSSES @ INTERIOR BEARING 8) FIRESTOP HVAC BOOT TO ATTIC @ M. BATH 9) PLN NOT HOLDING PER LEAKS UNDER 2ND FLOOR TUBS |