Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* LEFT GAS CARD |
|
| 08/23/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FIRE DAMPER ANGLE IRON NOT INSTALLED CORRECTLY ACCESS DOORS OPEN IDENTIFY ACCESS PANELS INSTALL DRAINS ON COOLERS AS PER INSTALL INSTRUCTIONS |
|
| 08/09/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BUSHING INSTALLED AT SEAL TIGHT PASS THROUGH |
|
| 05/15/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUSPENDED ROUGH DUCT OK TO PROCEED. 2. OK TO SHEETROCK ROOMS 111, 112, 106, 132, 131 3. DO A BETTER JOB INSTALLING FIRE DAMPER ANGLE IRON. 4. NEEDS TO BE FLUSH TO WALL. 5. FIRE CAULK AS NEEDED. 6. PROVIDE ACCESS DOORS IN DUCTS & CEILINGS 7. CONDENSATE NOT SIZED CORRECTLY. 8. SEE CHART IN 2003 UPC FOR PROPER SIZING. 9. REVISE PLANS AS NEEDED 10. PROVIDE FIRE DAMPER IN SHAFT OR RELOCATE FIREWALL |