Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED (1) BACKFLOW CERTIFICATION RECEIVED (1) BACTERIA REPORT FOR POTABLE WATER SUPPLY |
|
| 11/28/2007 | PLUMBING - FINAL | Partial Approval | 1. SECURE & SUPPORT EXPANSION TANK AT NORTH SHOP RESTROOM 2. INSULATE 8' IN & OUT OF THIS HEATER WATER PIPING 3. SEAL ALL PIPING PENETRATIONS OUT OF BUILDING 4. PROVIDE BACKFLOW CERTIFICATION FOR LANDSCAPING SUPPLY, WATER SUPPLY TO THIS DEVICE CANNOT BE GALVANIZED BY COPPER CONNECTION 5. INSULATE HOT & COLD PIPING 8' IN AND OUT OF WATER HEATER AT PARTS AREA 6. ABS PIPING NOT TO BE EXPOSED TO SUNLICHT AT INTERCEPTOR VENT LOCATION |
|
| 11/20/2007 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 11/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL ALL INSPECTIONS BEFORE CALLING FINAL |