Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ELECTRIC FINAL ON NEW BUILDING |
|
| 09/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK INSTANT HOTS 2. OK WATER HEATERS 3. FAN COIL UNIT IN ELEVATOR MACHINE ROOM CANNOT BE CORD & PLUG CONNECTED. CANNOT USE FLEXIBLE CORD FOR PERMANENT WIRING 4. OK ROOF AREA |
|
| 08/22/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK POWER IN SERVICE AREA 2. OK LIGHTING IN SERVICE AREA 3. OK GFI RECEPT BATHROOMS 4. OK DISCONNECT FOR PARTS MACHINE 5. OK EM LIGHT SWITCH GEAR ROOM 6. OK EXIT FIRST FLOOR WEST |
|
| 08/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK POWER 2ND FLOOR OFFICE AREAS 2. OK POWER 1ST FLOOR SHOP AREA OFFICES |
|
| 08/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CHECK EXIT FIRST FLOOR WEST 2. CHECK EM LIGHT IN SWITCHGEAR ROOM 3. CHECKED LIGHTING IN FRONT SHOWROOM, OFFICES, PARTS AND BACK OFFICE AREA. STILL NEED TO CHECK SHOP AREA. |
|
| 08/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL DISCONNECT FOR PARTS MACHINE 2. OK POWER FIRST FLOOR SHOWROOM, PARTS AREA, SERVICE DRIVE UP 3. NEED TO INSTALL INSTANT HOTS & RECEPT BATHROOMS 4. INSTALL INSTANT HOT JANITOR CLOSET 5. INSTALL RECEPT DATA ROOM 6. OK CEILINGS 141, 143, 144 |