Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/16/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC SUB-PANEL REQUIRES AN ISOLATED NEUTRAL BAR 2) JUNCTION BOXES CANNOT BE INCLOSED IN WALL CAVITY. INSTALL BOX EXTENSIONS 3) ELECTRIC SERVICE PANEL RISER SECURED WITH LOCK RINGS. YOU MUST INSTALL A BONDING BUSHING/CLAMP ON RISER TO PANEL |