Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/27/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) BRACE NOT TO BE WOOD. 2) GROUND ROD TO BE SUPLEMENTAL NOT PARALLEL. 3) BALANCE LOAD OF PANEL. ALLIS ON ONE PHASE. 4) WE HAVE GROUNDED RECEPTACLES ON AN UNDERGROUND SYSTEM/ CIRCUIT. 5) ELECTRICAL AND SERVICE NOT AS PER PLANS. |