Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02008
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BRACE NOT TO BE WOOD. 2) GROUND ROD TO BE SUPLEMENTAL NOT PARALLEL. 3) BALANCE LOAD OF PANEL. ALLIS ON ONE PHASE. 4) WE HAVE GROUNDED RECEPTACLES ON AN UNDERGROUND SYSTEM/ CIRCUIT. 5) ELECTRICAL AND SERVICE NOT AS PER PLANS. |