Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM02008
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/27/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. THE RISER MAST NEEDS TO BE BRACED. 2. THE ELECTRICAL SYSTEM WILL NEED TWO ( 2) 5/8'' X 8' GROUND RODS SET SIX (6) FEET APART. CONNECT THESE TO THE NEUTRAL BAR WITH A #4 SOL. COPPER GRD. WIRE. CORRECT & RECALL. | |
| 06/24/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 05/31/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* NO WORK HAS BEEN PERFORMED AT THIS TIME. |