Permit: T05CM02008

Parcel: 12217274A


Addresses:

3427 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T05CM02008

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/27/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :* 1. THE RISER MAST NEEDS TO BE BRACED. 2. THE ELECTRICAL SYSTEM WILL NEED TWO ( 2) 5/8'' X 8' GROUND RODS SET SIX (6) FEET APART. CONNECT THESE TO THE NEUTRAL BAR WITH A #4 SOL. COPPER GRD. WIRE. CORRECT & RECALL.
06/24/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
05/31/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :* NO WORK HAS BEEN PERFORMED AT THIS TIME.