Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM01999
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2005 | FRAMING | Approved | IVRS - Inspection :* | |
10/14/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED TO INSPECT CONCRETE FIX WEST WALL AT BATH, LEAVE REPAIR DETAIL ON SITE 2) TRUSS REPAIR ENCLOSED |
|
10/10/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/04/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ATTACH SHEAR TO H.D. GARAGE MAN DOOR 2) DUCT RESTRICTED LIVING ROOM CEILING 3) RE-DUE DRAIN CEILING LIVING ROOM, PIPE NOT IN HUB ALL THE CROOKED 4) DOES KITCHEN GET COUNTER 5) USE 3/4 DIAMETER BOLTS AT INTERIOR H.D.'S 6) 4 STUDS UNDER GIRDER REAR BEDROOM 7) SLAB CUT, BACK PITCH SHOWER DRAIN 8) BROKEN TRUSS ABOVE STAIR WELL 9) REMOVE NOTCH IN TOP PLATE AT CEILING NON BEARING AT STAIR 10) BACK PITCH AT SHOWER TRAP ARM SLAB CUT 11) NEED DWV TEST 12) GAS PRESSURE TEST HOLDING |
|
09/02/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |