Permit: T05CM01975

Parcel: 118081590


Addresses:

889 W CALLE CARASOL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM01975

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2005 PLUMBING - INTERMEDIATE Approved
08/15/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM #3050 NOT REQUIRED PER MIKE (HSP)
2) 8D1 DETAIL CALLS FOR BLOCKING BETWEEN TJI'S
3) RETEST WATER LINES GARAGE AREA
4) SEE INSPECTION DATED 8/11/05 CIRCLED ITEMS
08/11/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR
2) TRANSFORMERS NOT ALLOWED IN CLOSETS OR ATTICS
3) PLUMBERS TAPE NOT ALLOWED TO SUPPORT ABS
4) BLOWN FIRE BLOCK AT KITCHEN AND GARAGE
5) NAIL PROTECT ELECTRIC AT DEN
6) BLOWN FIRE BLOCK UNDER STAIRS
7) SW2 SHEARWALL MISSING A-BOLTS
8) MECHANICAL NOT PER PLAN
9) NO TEST ON DWV SYSTEM 2ND FLOOR
10) PROVIDE ENGINEER REPAIR FOR TJI'S IN GARAGE