Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL C OF O |
|
| 08/17/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/8" ID GAS FLEX CONNECTORS NOT ADEQUATE FOR 100,000 BTU. SEE LISTING ON FLEX. A/C 1,2,3,5,6 AND 7 RELOCATE ELECTRIC DISCONNECTS FROM BLOCKING ACCESS PANELS. PROVIDE MINIMUM 30" CLEARANCE. NEED TO TEST DUCT SMOKE DETECTOR |