Permit: T05CM01970

Parcel: 14111028B


Addresses:

8350 E OLD VAIL RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM01970

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 60 AND PSI TEST FROM VALVE ON EXISTING 5 PSI GAS LINE THRU TO NEW VALVES AT (8) ROOF TOP UNITS
2) WILL NEED TO INSPECT INSTALLATION OF REGULATER AND CONNECTION OT UNITS
07/26/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SYSTEM SHALL HOLD MINIMUM TEST PRESSURE WITH NO DROP
07/22/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
300 LB. TEST GAUGE NOT ACCURATE IN 5LB. INCREMENTS - PROVIDE A 100 LB. GAUGE
07/19/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) MEDIUM PRESSURE GAS PIPING REQUIRE 60 PSI TEST MINIMUM
2) WHERE UNIONS ARE NECESSARY-LEFT AND RIGHT NIPPLE COUPLINGS SHALL BE USED