Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER RON |
|
| 10/10/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER RON |
|
| 10/06/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ACCESS TO A/C CONDENSOR ELECTRIC DISCONNECT OBSTRUCTED BY CONDENSORS-TWO UNITS 2) A/C CONDENSOR PLATFORM MUST BE 3" ABOVE FINISHED GRADE 3) NO WATER HEATER T & P LINE 4) GARAGE PERSONNEL DOOR MUST BE A MINIMUM 1 3/8" SOLD CORE 20 MINUTE RATED FIRE DOOR SELF CLOSING AND LATCHING 5) PARTIAL BEAR BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS 6) MAXIMUM ALLOWED ELECTRIC DEVICES ON 15 AMP ARC FAULT CIRCUIT IS 13 EXCEEDED TO MORE THAN 18 |