Permit: T05CM01948

Parcel: 20564067A


Addresses:

11350 E RITA RD

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
09/19/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
09/16/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UFER CLAMP TO BE ALL BRASS LISTED FOR DIRECT BURIAL
2) HORIZ STEEL NOT SUPPORTED ENOUGH, MAINTAIN 3" TO EARTH
3) VERTS MAJORITY OF WALLS ARE (A) = 32" O.C. VERTS. YOU DON'T HAVE IN PLACES, TRANSVERSE BARS ARE SAME SPACING AS VERTS (SEE SCHEDULE)
4) REMOVE ROCKS AND SPOILS FROM FTGS
5) NEED TO KNOW THE ACTUAL HT. OF YOUR RESTRAINING WALL, 3 ITS FTG DEPTH, WHAT SPACING OF VERTS ARE YOU USING
6) MAKE SURE VERTS ARE ALIGNED, 6" STEM BARS TOO BE CENTERED
7) SOME VERTS NOT TIED TO HORIZ
8) IN SUMMARY YOU NEED TO CLEAN UP FTGS, (SECURE AND ALIGN) STEE IF STEEL IS OUT OF STEM EPOXY FIX WILL BE REQD. PER THE ENGINEER
9) COPY OF SOIL REPORT (SENT TO) FILES
09/15/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 5/9 <16> 5# 4S EA WAY GARAGE
<G> 4# 4S EA WAY GARAGE
2) 4/9 <2> MISSED COL FTG. LIV ROOM SO. WALL
KIT SO. WALL
3) YOU NEED A COMPACTION REPORT. THIS PAD ISN'T LEVEL, WHAT IS FINISH GRADE IMPORTANT FOR RETICAINING WALL DETAIL, CAN'T USE THAT DETAIL UNTIL F/FLR IS ESTABLISHED
4) STEPPED FOOTINGS SHOULD BE LEVEL TOP AND BOTTOM YOU MAY HAVE A SLOPE OF 1 VERT FOR 10" HORIZ YOU HAVE MORE THAN THAT, FTG 10" THICK SOME PINS ARE LESS, TOP OF FTG GRADE APPEARS NOT TO BE LEVEL
09/15/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) SEE LAST INSP - SAME ISSUES
09/13/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*