Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER SERVICE IS ENERGIZED AND ALL WIRING IS COMPLETE |
|
| 03/14/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND METER BASE NEC 250.92 2. INSTALL HOLD DOWN FOR MAIN BREAKER NEC 408.16 (F) 3. DRIVE GROUND RODS FLUSH NEC 250.53 (G) 4. INSTALL WARNING RIBBON FOR SERVICE CONDUCTORS NEC 300.5 (D) (3) (DONE) |
|
| 03/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |