Permit: T05CM01871

Parcel: 11108220A


Addresses:

3755 E FLOWER ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01871

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALLED 792-0029 AND NO ANSWER
SPOKE WITH ROLAND AND JESSE
THEY CANNOT MEET HERE
A REFEE MAY BE ACCESSED NEXT
INSPECTION IF WE CANNOT ACCESS UNITS.
01/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DOOR LOCKED
06/15/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
KIT RECEPT -- FIX
STAIR LIGHT -- REPAIR
06/06/2006 ELECTRIC - FINAL Cancelled CANCELLED PER KIM OF LA COCQ CONSTRUCTION #792-0029
06/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OPEN J-BOX IN BEDROOM.
2. WASHER NEEDS GFI PROTECTION OR SINGLE RECEPTACLE.
3. FINISH ALL LIGHT FIXTURES AND INSTALL BULBS.
4. HAVE SEVERAL LOOSE DEVICES AND DON'T USE DRYWALL SCREWS TO MOUNT DEVICES (8/32 OR 6/32).
5. INSTALL DEVICE COVERS.
6. USE BOX EXTENDERS FOR DISPOSAL.
7. INSTALL D.W. TAILS - 4' MAX.
8. CEILING FAN NOT WORKING
9. UPSTAIRS BATH GFI NOT WORKING.
10. PATCH AROUND EQUIPMENT IN WALLS AROUND ROOFTOP.
11. SECURE BOND WIRE ON ROOF -- HOW IS GAS BONDED?
12. INSTALL DISCONNECT FOR HOUSE LIGHTING.
13. A.C DISCONNECTS DO NOT HAVE ENTRY CLEARANCE.