Permit: T05CM01867

Parcel: 11108220A


Addresses:

3767 E FLOWER ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T05CM01867

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2007 ELECTRIC - CABLE DROP Approved PER EL FINAL
07/20/2006 ELECTRIC - CABLE DROP Denied 1. SEAL HOLE BOTTOM OF PANEL
2. CIRCUITS TO BE LABELED AS TO WHICH BLDGS LIGHT FED
3. ONE CIRCUIT NOT MARKED
4. LIGHTS UNDER CARPORT TO BE APPROVED FOR WET LOCATION.
5. PANEL SHOWS 2 EXTRA CIR'S 1 LAMPS IN CARPORTS
6. CIR FOR LAMP POST AT DUMPSTER MISSING
7. PLAN CALLS FOR TIMER TO BE PROTECTED IN METAL WATERPROOF ON SITE INSTALLED IS A PLASTIC PHOTO CELL.
8. LUMEN CAPACITY FOR BLDG. LIGHTS IS ONLY 750 LUMENS PROVIDE LUMEN OUTPUT FOR BLDG. LIGHTS.
9. CONTRACTOR TO PROVIDE LETTER ON OMISSION OF DUMPSTER LIGHTING, OMISSION OF 2 CIRCUITS ON OWNER'S PANEL, OMISSION OF TIMER FOR PHOTO CELL AND CUT SHEET OF BLDG FIXTURE
06/15/2006 ELECTRIC - CABLE DROP Approved PER EL FINAL
06/15/2006 ELECTRIC - CABLE DROP Approved PER EL FINAL
01/20/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
01/13/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*