Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM01833

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :* OK FOR TEMP C OF O. 1) WAITING ON PLAN REVISIONS
07/12/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/11/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/08/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 2) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 3) LIGHT FIXTURES TO BE SECURILY ATTACHED TO GRID 410.16 4) GROUND JUNCTION BOXES. 5) LIGHT FIXTURES IN JUMPING CASTLE ROOMS ARE NEW THEY ARE NOT ON PLANS. WE HAVE 400 W PER LIGHT. PLEASE RE VISE PLANS AND LOADS. 6) REVISE PANEL SCHEDULE. 7) CORD NOT TO PASS THROUGH WALLS 400.7 & 400.8 8) VDV CABLEING TO BE SUPPORTED PER 725.6 & 800.6