Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM01833
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR TEMP C OF O. 1) WAITING ON PLAN REVISIONS | |
07/12/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/11/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
07/08/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 2) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 3) LIGHT FIXTURES TO BE SECURILY ATTACHED TO GRID 410.16 4) GROUND JUNCTION BOXES. 5) LIGHT FIXTURES IN JUMPING CASTLE ROOMS ARE NEW THEY ARE NOT ON PLANS. WE HAVE 400 W PER LIGHT. PLEASE RE VISE PLANS AND LOADS. 6) REVISE PANEL SCHEDULE. 7) CORD NOT TO PASS THROUGH WALLS 400.7 & 400.8 8) VDV CABLEING TO BE SUPPORTED PER 725.6 & 800.6 |