Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
07/30/2005 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
1) NEW 4" BLDG SEWER P.O.C. TO EXISTING BLDG SEWER IS OK
2) OK TO BACKFILL TRENCH
07/26/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) DWV WATER TEST IS OK
2) CORRECTIONS FOR U.G. SOIL WITHIN STRUCTURE IS OK
3) OK FOR BACKFILL
4) SHALL SEE FINAL CONNECTIONS TO HCS AND EXISTING BLDG SEWER
07/21/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE A SAN-TEE FOR THE TUB WASTE AND PROVIDE A L-SWEEP BELOW THE SAN-TEE
2) SHALL REPLACE 3 X 2 SAN-TEE FOR LAV WASTE
07/20/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE DIRECTIONAL FITTINGS FOR WATER CLOSET AND TWO WAY CLEANOUT
2) RE-TEST THE SYSTEM
07/14/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE A WATER TEST ON UNDERGROUND WASTE AND VENT SYSTEM WITH MINIMUM 10' HEAD
2) SHALL EXPOSE ALL 4" WASTE LINE IN TRENCH
3) SHALL REMOVE AND PROVIDE DRECTIONAL FITTINGS FOR TWO WAY CLEANOUT
4) SHALL INSTALL CLOSET BEND FOR WATER CLOSET AND P-TRAP FOR TUB AND SHOWER