Permit: T05CM01807

Parcel: 11711096E


Addresses:

120 N STONE AV #200

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/18/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
08/02/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DO NOT CONNECT PRIMARY AND SECONDARY DRAINS INTO COMMON PIPE. NEED TO RUN SEPERATE LINES. DO NOT BLOCK CLEARANCES TO FAN COIL-MAINTAIN CLEARANCE
2) 2ND FLOOR LOBBY-OK TO SHEETROCK
07/07/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* OK TEMP C OF O INCOMPLETED AREA.
07/06/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) ARE EXISTING OLD ROOF TILES PLENUIM RATED? 2) HOW IS SPACE ( ATTIC) BEING ISOLATED FROM CONDITIONED ( COMFORT ZONE) BELOW GRID, NORTH WEST CONF RM??. 3) SEAL OPENING ALONE PLENIUM
07/01/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILING TILES ROOM 200 ONLY
06/21/2005 MECHANICAL - INTERMEDIATE Partial Approval 1) OK TO COVER REST RM LIDS. 2) LETTER FROM ARCHITECT /ADD FIRE DAMPERS
06/20/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/16/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECK EXISTING FIRE DAMPERS
06/09/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* JOB PROGRESSING, SEAL ALL JOINTS.