Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2005 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/05/2005 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) UNABLE TO LOCATE PLUMBER OR GENERAL CONTRACTOR-HE FOUND ME 2) SINKS AND URINALS INSTALLED PER RED LINES 3) NOTE: CONTRACTOR TO REPLACE JIM CAPS WITH ABSO SOLVENT WELD CAP |
|
| 06/23/2005 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BELOW FLOOR PLUMBING FOR RESTROOMS OK. 2) URINALS AND SINKS NOT INSTALLED PER PLAN NO REDLINES ON SITE. 3) CHANGING ??? TYPES FROM ABS TO N/IT BACK TO ABS BACKT TO N/H-NOT GOODF INSTALLATION PRACTICE. IMPROPER USE OF FITTINGS NOT APPROVED. REMOVE 4" N/H BLAKE TEE ON ITS BACK. 4) INSTALL IN A WORKMANSHIP LIKE MANNER. | |
| 06/09/2005 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. RESTROOMS # 208 & 209 OK TO COVER WITH EXCEPTION: SERVICE SINK IN # 212 NOT REPLUMBED CORRECTLY OK TO COVER RESTROOMS-EXCEPT SINK. 2) DEMO'D SINK IN # 230 OK. 3) PLUMBING IN # 224 & 225 OK TO COVER. | |
| 06/07/2005 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) REMEMBER : CHANGES OF DIRECTION, CHANGES OF ELEVATION AND THE END OF BRANCHES_ THEN EVERY SO MANY FEET ACCORDING TO TABLE 3-1 94 UPC. 2) REVIEW INSULATION REQUIREMENTS. 3) NO TEST AT THIS TIME. |