Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/21/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
2) ITEM 03089 NOT APPLICABLE PER INSPECTOR-NO MEDICAL GAS IN THIS SUITE
09/15/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RELOCATE 1 A/C UNIT TO ALLOW CLEAR ACCESS TO THE ELECTRICAL CONTROLS PANELS ON A/C UNITS. UNITS NOT LAYED OUT AS PER PLANS. RELOCATE 1 SEWER VENT FROM BLOCKING ACCESS TO SERVICE PANEL.
PROVIDE FRESH AIR INTAKE ON A/C UNITS.
BLOCK AND CLAMP PVC EVERY 4' AND PAINT WITH LATEX PAINT.
PROVIDE A SERVICE RECEPTACLE WITHIN 25' OF MECHANICAL EQUIPMENT.
BLOCK AND CLAMP ALL ELECTRICAL CONDUITS ON THE ROOF PER N.E.C. AND BOB SUBA.
PERMANENTLY IDENTIFY A/C UNIT (AC-1, AC-2, ETC)