Permit: T05CM01789

Parcel: 134242860


Addresses:

6601 E 22ND ST #101

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/26/2005 BUILDING - FINAL Approved IVRS - Inspection :*
10/20/2005 BUILDING - FINAL Partial Approval IVRS - Inspection :*OK FOR C OF O WHEN PLUMBING FINALES
RESTROOMS OFF HALL 104 NOT REQUIRED TO BE ACCESSIBLE PER 3409.3 IBC 2003 ( SEE REVISED PLAN) PLAN STILL SHOWS ROOMS 117 AND 118 AS ADA THIS WAS A TYPOGRAPHICAL OVERSIGHT.
10/06/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*DENIED SEE NOTES 2,3,5 FROM 9/21/05
09/21/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTES DATED 7-11-05 (PIMA COUNTRY REQUIREMENT)
2) PROVIDE PLUMBING FINAL AND ALL C OF O FINALS
3) ALL DOORS, DOOR HARDWARE AND GRAB BARS IN RESTROOMS MUST BE INSTALLED
4) IF RESTROOM 116 IS TO BE ADA THEN DOOR MUST SWING IN PER PLAN
5) IF RESTROOMS OFF OF HALL 104 ARE TO BE ADA THEN 42" WIDE HALL IS REQUIRED. FOR ANYTHING ELSE APPEAL TO BUILDING OFFICIAL IS REQUIRED. PLEASE PROVIDE APPROVED APPEAL FROM BUILDING OFFICIAL FOR <2> REVIEW.
07/11/2005 BUILDING - FINAL Not ready for Inspection 12" ADDRESS DISPLAY REQUIRED ON BUILDINGS