Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 05/15/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALLS FOR 5" X 15" GLB FOR HEADER 2) MUST OPEN UP BOTTOM OF FRAME COLUMN TO VERIFY BOLTS INTO CONCRETE 3) NEED POSITIVE CONNECTION FROM FOUNDATION VERTICALLY TO RAFTER 4) PLAN CALLS FOR LEDGER TO BE NAILED AT 16" SACING TO EXISTING 5) ALSO INSTALL 36" STRAP GLB TO FRAM COLUMN PER PLAN 6) CANNOT LOCATE ON PLAN WHAT SPACING 2" X 8" RAFTERS ARE TO BE 7) NEED LADDER TO INSPECT ROOF 8) STOPPED INSPECTION 9) COMPLETE ALL AND RECALL |