Permit: T05CM01761

Parcel: 140383490

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/08/2005 FRAMING Approved IVRS - Inspection :*
09/01/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO GAS PRESSURE TEST
2) NAIL BATH WET VENT MUST BE 1 SIZE LARGER THAN MINIMUM FOR W/C
3) SECURE 4 GANGE ELECTRIC BOX 2 GNDS?
4) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES
5) PLUMBING OUT OF WALL CAVITY MASTER TUB
OK TO INSULATE
08/25/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
N/R PER LLOYD
08/19/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) TWO STUDS NOT NAILED TO LATH
2) PROVIDE 1/4" CLEARANCE TO LATH AT POPOUT CORNERS
3) NO GAS TEST
4) NO DWV WATER TEST
5) SECURE 4 GANG ELECTRIC BOX ON TWO C-B(?)
6) BLOCK RETURN AIR
7) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
8) EDGE NAILING OF WIRES IS NOT ALLOWED
9) W/C REQUIRES 15" TO FINISHED WALL
10) SHEAR TRANSFORM BLOCK BROKEN AT M/BR SHEAR WALL
11) STOPPED INSPECTION, TOO MANY ITEMS