Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO GAS PRESSURE TEST 2) NAIL BATH WET VENT MUST BE 1 SIZE LARGER THAN MINIMUM FOR W/C 3) SECURE 4 GANGE ELECTRIC BOX 2 GNDS? 4) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES 5) PLUMBING OUT OF WALL CAVITY MASTER TUB OK TO INSULATE |
|
| 08/25/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* N/R PER LLOYD |
|
| 08/19/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) TWO STUDS NOT NAILED TO LATH 2) PROVIDE 1/4" CLEARANCE TO LATH AT POPOUT CORNERS 3) NO GAS TEST 4) NO DWV WATER TEST 5) SECURE 4 GANG ELECTRIC BOX ON TWO C-B(?) 6) BLOCK RETURN AIR 7) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 8) EDGE NAILING OF WIRES IS NOT ALLOWED 9) W/C REQUIRES 15" TO FINISHED WALL 10) SHEAR TRANSFORM BLOCK BROKEN AT M/BR SHEAR WALL 11) STOPPED INSPECTION, TOO MANY ITEMS |