Permit: T05CM01742

Parcel: 13815026C


Addresses:

230 E TETON RD #01

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/17/2007 PLUMBING - SEWER HCS CONNECT Approved
01/26/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
OK TO COVER SEWER, TO PROP LINE - BACKFILL TO BOTTOM OF WATER LINE SO THAT WATER LINE RESTS ON A FIRM BASE
01/24/2006 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*PROVIDE 2 % SLPE ON ALL SECTIONS OF SEWER
PROVIDE 1' HORIZONTAL & VERTICAL SEAPARATION OF SEWER AND PVC WATER PIPING
SUPPORT WATER PIPING
PROVIDE TRACER WIRES.