Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL LUGGING OF A14 AND A12 WIRE ON NEUTRAL BAR NOT ALLOWED 2) MAXIMUM ALLOWED FOR A/C CONDENSOR FUSE/CB IS 30 AMP-40 INSTALLED 3) PLUGGING "B" VENT AT WATER HEATER NOT ALLOWED 4) SECURE GAS LINE AT WATER HEATER IN WALL |
|
| 10/04/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |