Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM01726
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/21/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*FLEX WATER HEATER -SO CORD CANNOT BE USED AS PERMANENT WIRING METHOD 400 NEC WH DOES NOT NEED FLEXIBILITY MISSING DISCONNECT SWITCH REAR COMPRESSOR. |
|
11/18/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*THE INSTALLATION OF WATER HEATER IS TO BE DETERMINED BY BUILDING INSPECTOR TO BE IN ROOM OUT OF CEILING AREA-CANNOT USE CORD ABOVE CEILING NEC 2002 400 7 & 8 FAN'S IN WALK INS REQUIRED TO AHVE DISCON MEAN W/IN SIGHT OR LOCK OUT AT PNL SEAL INSIDE PENETRATION OF RACE WAY INTO WALKING |