Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | ||
| 09/28/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 09/09/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) MATERIAL CHANGES TO THE PLAN MUST BE APPROVED BY THE ARCHITECT 2) OK TO COVER SUBJECT TO ARCHITECT APPROVAL OF MATERIAL TYPE |
|
| 09/06/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PEX HAS BEEN APPROVED FOR USE INSIDE THE BLDG. THE APPROVED PLAN STATES THAT OUTSIDE THE BLDG SHALL BE SCHEDULE 40 PVC-FOUND NO REVISION ALLOWING PEX YARD WATER ON THE PLAN 2) CONTRACTOR TO PAY RE-INSPECTION FEE |
|
| 08/30/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) NOT INSTALLED PER PLAN-PLAN SHOWS 1" SCHEDULE 40 TO PVC YARD WATER PIPING 2) IS COPPER AT SERVICE TO BE USED AS A GROUND ? IF SO, PLEASE EXTEND TO TEN FEET |
|
| 08/11/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 08/09/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* |