Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2005 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
08/29/2005 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHIRT ADDED TO BOTTOM OF LISTED HOOD WITHOUT APPROVAL-DOES NOT MEET CODE SECTION LISTED ABOVE 3) RUN CORRECTION THRU MECH CODE APPROVAL ACCEPTANCE |
|
08/22/2005 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2000 IMC - SEC. 507.12 2) MAX DISTANCE, COOKING SURFACE TO BOTTOM OF HOOD, 48" (4 FEET), NOT 5' FEET 3) SHT. A1.1 A WHERE IS RATES/CHASE? OR 1 1/2 HR. FIRE WRAP? |
|
08/16/2005 | MECHANICAL - HOODS | Cancelled | CANCELLED PER RYAN THE CONTRACTOR 602-518-3520 | |