Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) DWV WATER TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE. 3) OK TO BACKFILL TRENCH. | |
| 07/07/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT REDUCE THE TRAP ARM FOR P-5. 2) RE TEST THE SYSTEM |
|
| 07/06/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) P TRAP FOR P-5 REQUIRES A 2" TRAP. OR PROVIDE A FLOOR SINK WITH A 3" OUTLET. ONLY ONE PIPE SIZE LARGER THAN THE OUTLET OF FIXTURE ALLOWED FOR TRAP SIZE. 2) REMOVE FERNCO COUPLING. 3) RE TEST THE SYSTEM. |