Permit: T05CM01698

Parcel: 12209003A


Addresses:

3923 E PIMA ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM01698

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2005 ELECTRIC - ABOVE CEILING Approved
09/07/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/06/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/01/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT BOXES TO GRID FOR PLUG
2) SUPPORT CONDUIT WITHIN 3' OF BOXES
3) USE A BOX APPROVED FOR SUPPORT OF CEILING FAN
4) SUPPORT M/C CABLES PER 334.30 AND 300.11
5) FILL UNUSED OPENINGS IN BOXES
6) BOX/CORD IN CENTER OF KITCHEN AND FANS NOT ON PLANS
7) NEED HOOD INTERLOCK AND COOLER BOX AS PER PLANS-NOTES 15 AND 16
8) FINISH PREVIOUS ITEMS #7
08/31/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2) WHERE IS CIRCUIT, RECEPTACLE AND LOAD CALC'S FOR ICE MACHINE ?
3) DID CIRCUIT FOR SODA MACHINE GET MOVED ?
4) RELOCATED LIGHTS TO BE ATTACHED TO GRID 410.16
5) CONDUCTOR OVER FILL IN JUNCTION BOX
6) INSTALL BOX COVERS
7) SUPPORT VDV CABELING 6' INTERVALS 725.6, 800.6 AND 300.11
8) PLEASE VERIFY HOOD INTERLOCK
9) PROVIDE ROOF ACCESS