Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM01670
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2005 | FRAMING | Approved | IVRS - Inspection :* | |
06/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT BOOT ABOVE CEILING BY M/BR 2) FIRESTOP CHASE NORTH OF M/BR ARCH 3) BATHROOM LAV MUST HABE 1/4 FT PITCH 4) BEARING WALL STUDS CANNOT BE NOTCHED MORE THAN 25 PERCENT-REPLACE 5) A03C 31-32 BRACE MISSING 6) A04D RAT RUN MISSING 7) SHIM HEADERS 6) OK TO INSULATE |
|
06/21/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) BANG PLATE ROMEX IN LIVING ROOM 2) SMOKE DETECTOR ABOVE DROP 3) LOWER DUCT LIVING ROOM TRUSSES FURRED 4) FIRE BLOCK SIDE OF CHASE FIREPLACE 5) BACK PITCH LAV VENT NORTH SIDE 6) CONCRETE TUB BLOCK OUTS 7) SHIM ALL 3 PT BEARING A03 TRUSSES INCLUDE 1/2 FRONT GABLE 5 TOTAL, ADD RAT RUNS 8) A04A FLAT SHIM REQUIRED, RAT RUN A04D 9) FINISH # 3 SHEAR BLOCKS KITCHEN 10) P.T. PLAN STATES NO LOAD ON SLAB UNTIL CABLES TENSIONED 11) DWV H20 OK 12) DRIP EDGE ON ROOF AT PORCH HOLD BACK FOR STUCCO 3/8" |